Network-M2のファームウェア 3.1.15 が公開されました。
【重要】ご使用のファームウェアが2.0.5以下(1.x.x含む)の場合、一度2.1.5にアップグレードしてから、3.x.xへアップグレードしてください。2.0.5以下(1.x.x含む)から3.x.xへの直接アップグレードは推奨されていません。
バージョンアップを実施すると、ネットワークカードは再起動しますが、UPS本体は出力を停止することなく稼働し続けます。
以下、Eaton発行のリリースノート(原文)
========================================================================================== Firmware release notes for Eaton Gigabit Network Card for UPS (Network-M2, P/N 744-A3983) Firmware : Release 3.1.15 Date : 2024/10/16 Eaton (c) 2024 ========================================================================================== Upgrade/Compatibility: This section describes the considerations for upgrading from a previous release. It is not recommended to upgrade to 3.x.x from 1.x.x directly. 1.x.x firmware versions should first be upgraded to 2.1.5 as an intermediate step and then upgraded to 3.x.x. Note that upgrading to 2.x.x from any 1.x.x firmware revision will clear all alarms and events from the user interface. A backup of these alarms and events is available through RESTful API. See https://www.eaton.com/network-m2 for detailed RESTful API documentation. Earlier versions can be upgraded to 3.1.15 according to the procedure described in the manual. Downgrade from 1.6.x or above to 1.5.x or below is not possible. Beyond this limitation, downgrade to earlier versions is possible but not recommended. =============================== Release 3.1.15 October 2024 =============================== Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher, VPM 6.4.0 and higher Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9130, FERRUPS FX, 9E, 93PM (fw 1.48->), 93PM G2, 93PS (fw 2.50->), 91PS, 93E 15-80 EMEA (fw 8.00.01->), 93E G2 EMEA (fw 4.0.20->) Supported ATS: Eaton EATS115, EATS16, EATS120, EATS220 Additions: - Add Energy Aware Active status - Add Energy Aware Available status - Energy Aware label in UI for available and inactive cases Fixes: - Update openssh to 9.8p1 - 9130 UPS segment synoptic issue in battery mode - Optimized CPU ressource usage - Improved UPS firmware upgrade compatibility - Fixed missing UPM data in KDP email attachment - Negative temperature values from EMP are now handled correctly to avoid battery over temperature alarms - Fixed ATS communication issue - Increased the time out for request reports and descriptors from 1 sec to 5 sec. - Limited the number of UPMs to 15 in the sub module map
Network-M2 ファームウェアアップグレード手順
https://www.eaton-daitron.jp/techblog/10083.html