Intelligent Power Protector (IPP) Version 1.61 リリース

Intelligent Power Protector (IPP) のバージョン1.61が公開されました。

◎新ネットワークカード「Network-M2」に対応するためのバージョンアップです。

是非、この機会に最新版1.61へバージョンアップを実施してください。

以下、Eaton発行のリリースノート(原文)

===============================================================================
 Release note Intelligent Power Protector 1.61 for Windows
 (August 2018)
===============================================================================

New features:
=============
* New Network-M2 communication card compatibility : authentication by certificate exchange / credentials
* New Shutdown delay option is available on IPP when Network-M2 card is connected as Power Source (please refer to Card On line help)

Pairing Guidelines: (New Network-M2)
===================
* Card Version 1.4.3 recommended to ease pairing Software and card
* Information about Pairing are mentionnend on Network-M2 card, (not on IPP on line help) 
* For Pairing, Credentials must not be used for version below 1.4.2 (included). Potential limitations below :
	* The user MUST do the Pairing from the card. 
	* If user sets Credentials from IPM, he will not be able to monitor the card  
	* In some cases, removing and rescanning the card is not enough	: IPM servce restart is required


Known issues:
=============

* After IPP Upgrade Network-M2 card cannot be discovered : fresh install is mandatory
* On Network-M2 side, Event messages severity have been modified since Network-MS. Behavior on IPP is then impacted 
* On Network-M2 side, we have the 30 IPP simultaneous connections limitation.
* On Network-M2 Card F/W version is not displayed

Eaton IPP ダウンロードサイト
http://powerquality.eaton.com/Support/Software-Drivers/default.asp

ソフトウェア&ファームウェア ダウンロード手順
https://www.eaton-daitron.jp/techblog/5591.html